GFP - On Delay Timer

GFP - On Delay Timer

Main Image
Product Images Product Videos
Main ImageMain Image
Video
Description: Delay On Timer

Details:

The GFP is a Delay On timer with adjustable time range in the ratio of 10 to 100%. There are options of 7 voltage ranges AC/DC and 9 time ranges.
  • DELAY ON TIMER
  • 7 VOLTAGE RANGES
  • 9 ADJUSTABLE TIME RANGES






Selection:

For the product to suit your application please see the selection chart below or contact sales:
Use Filter menus to browse products - 1 Filter(s) Set
Product Ref Supply VoltageTime RangeOutput ContactsEnclosure Typeabout enclosure typesTiming Function
GFP1101add to basket110Vac0.3 - 3secs1 pole C/O5Delay On
GFP2101add to basket110Vac1 - 10secs1 pole C/O5Delay On
GFP3101add to basket110Vac3 - 30secs1 pole C/O5Delay On
GFP4101add to basket110Vac6 - 60secs1 pole C/O5Delay On
GFP5101add to basket110Vac12 - 120secs1 pole C/O5Delay On
GFP6101add to basket110Vac18-180secs1 pole C/O5Delay On
GFP7101add to basket110Vac1 - 10mins1 pole C/O5Delay On
GFP8101add to basket110Vac3 - 30mins1 pole C/O5Delay On
GFP9101add to basket110Vac6 - 60mins1 pole C/O5Delay On


Trip Delay Timer
Where fitted the ‘Trip Delay Timer’ will inhibit the output contacts from releasing immediately a fault is detected.
The trip delay time is adjustable up to either 10 or 30 seconds depending on the model and will be either a ‘Standard’ delay or a ‘True’ delay type.
The 'Standard' delay type will require around 50% nominal supply voltage to be maintained for its operation, in the case of a total loss of power the unit
will trip with a minimal delay of approximately 0.5 seconds. This type of timer will allow the unit to ride through a short term voltage dip but not a total
power loss.
The 'True' delay timer is not dependent on the supply voltage for its operation. The timing function will be available in the case of either a partial or total
supply failure. This type of timer will allow the unit to ride through either a short term voltage dip or a total loss of power lasting up to 30 seconds.
Power On Delay Timer
Where fitted, the ‘Power On Delay Timer’ will delay the output contacts from energising immediately the supply voltage is applied to the unit for a period
of up to 30 seconds.
The supply voltage will have to satisfy the conditions set by the supply monitoring relay for a healthy supply continuously for the ‘Power On Delay’ timing
period before the output contacts will energise.
If the unit detects a fault and releases the output contacts the supply voltage will once again have to satisfy the requirements of a healthy supply continuously
for the ‘Power On Delay’ timing period before the output contacts will re-energise.